A 3-phase induction motor draws 1000 kVA at power factor of 0.8 lag. A synchronous condenser is connected in parallel to draw an additional 750 kVA at 0.6 power factor leading. Then the power factor of the total load supplied by the mains is
A
Reactive power absorbed by supply is 600 kVAR.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
Reactive power delivered by supply is 600 kVAR.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
Supply power factor is unity.
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
Supply power factor is 0.9 lagging.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution
The correct option is C Supply power factor is unity. Complex power can be represented as,