Question

A power system has a circuit breaker connecting a large system, (initially open) to other system between bus 2 and bus 3. The system B three-phase fault level at bus 3 under the condition is unknown. After closing circuit breaker, the 3ϕ fault level at bus 1 was found to be 6 pu. The new 3ϕ fault level at system bus 3 after interconnection will be _______pu.(Assume prefault voltages to be 1 pu at all buses).


  1. 7.71

Open in App
Solution

The correct option is A 7.71
Drawing single line diagram, assuming system B reactance be X,



If fault occurs at bus 1 after reactance,



Thevenin impedance, Zth=(0.2+0.1)| |(0.2+X)

=(0.3)(0.2+X)0.5+X

Also, per unit fault current =1Zth=6 pu

16=(0.3)(0.2+X)0.5+X

0.5 + X = (1.8) (0.2 + X)
0.8 X = 0.5 - 0.36 or X = 0.175 pu

Now using X = 0.175 pu, finding fault level at bus 3 after interconnection

New, Zth pu=(0.5)(0.175)0.675=0.1296 pu

If=1Zth pu=7.71 pu