LFC: Single Area Control
Trending Questions
Q. Given a single area with two generating units.
The units share a load of P1=200MW, P2=500MW. The units are operating in parallel to share a load of 700 MW at 50 Hz frequency. The load is increased by 130 MW with B = 0, The value of new frequency caused by steady state frequency deviation is _______ Hz.
Unit | Rating | Speed drop R (per unit on unit base) |
1 | 400 | 0.04 |
2 | 800 | 0.05 |
The units share a load of P1=200MW, P2=500MW. The units are operating in parallel to share a load of 700 MW at 50 Hz frequency. The load is increased by 130 MW with B = 0, The value of new frequency caused by steady state frequency deviation is _______ Hz.
- 49.75
Q. Consider a power system with three identical generators. The transmission losses are negligible. One generator (G1) has a speed governor which maintains its speed constant at the rated value while the other generators (G2 and G3) have governors with a droops of 5%. If the load of the system is increased, then in steady state.
- Generation of G2 adn G3 is increased equally while generation of G1 is unchanged.
- Generation of G1 alone is increased while generation of G2 and G3 is unchanged.
- Generation of G1, G2 and G3 is increased equally.
- Generation of G1, G2 and G3 is increased in the ratio 0.5 : 25 : 0.25