CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 10-bus power system consists of four generator buses indexed at G1, G2, G3, G4 and six load buses indexed as L1, L2, L3, L4, L5, L6. The generator-bus G1 is considered as slack bus, and the load buses L3 and L4 are voltage controlled buses. The generator at bus G2 cannot supply the required reactive power demand, and hence it is operating at its maximum reactive power limit. The number of non-linear equations required for solving the load flow problem using Newton Raphson method in polar form is
  1. 14

Open in App
Solution

The correct option is A 14
Total number of buses 10
G1 slack bus
G2PQbus (because reactive power limit is reached )
G3G4}PVbus
Minimum number of non linear equations to be solved
= Number of unknown bus voltage variables
(2×1042)=14

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Newton-Raphson (NR) Method
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon