A 10 hp, 230 V, 60 Hz, 3-phase, star connected, synchronous motor delivers full load at a power factor of 0.707 leading. The synchronous reactance of the motor is j5Ω/phase. The rotational loss is 230 W and the filed winding loss is 70 W. The generated voltage per phase is ______(take 1hp=746W)

A
132.790V
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
248.822.8V
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
168.1511.8V
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
221.1011.2V
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B 248.822.8V
The power output : Po=10×746=7460W

Power developed : Pd=Po+Pr

=7460+230=7690W

Since there is no copper loss in armature winding, the power supplied by 230 V alternative current source is 7690 W.

Ia=76903×230×0.707=27.3A

Total power input :Pin=7690+70=7760W

Va=23003=132.790V

Ia=27.345A

Generated voltage per phase is
Ea=132.790(27.345)j5

=248.822.8V