wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 100 MVA, 50 Hz synchronous generator having inertia constant H = 5 kW-s/KVA on full load at unity power factor. The load is suddenly reduced to 60 MW. Due to time lag in governor system, the steam valve begins to close after 0.5 second. The change in frequency that occurs in this time is ______Hz.
  1. 1

Open in App
Solution

The correct option is A 1
The rating of the machine G = 100 MVA

Intertia constant, H = 5 kW-s/KVA
= 5 KJ/KVA = 5 MJ/MVA

Kinetic energy stored in the rotating parts of generator and turbine at synchronous speed (f = 50 Hz)
=HG=5×100=500 MJ

Excess power input to the generator shaft before the steam valve begins to close,

=10060=40 MW

Excess energy transferred to rotating parts in 0.5 sec
40×0.5=20 MJ

Since, Kinetic energy, K.E f2
So, frequency at the end of 0.5 sec

f2=f1Total energy stored in 0.5 secEnergy stored at sychronous speed

f2=50500+20500=50×1.02=51 Hz

Change in frequency =f2f1
=5150=1 Hz

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Kinetic Energy and Work Energy Theorem
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon