A 1000 kVA, 6.6 kV, 3-phase star connected synchronous generator has a synchronous reactance of 25Ω per phase. It supplies full load current at 0.8 lagging pf and rated terminal voltage. The terminal voltage (line) for the same excitation when the generator supplies full load current at 0.8 leading pf is_________.

A
9.15 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
11.15 kV
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
2.48 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
6.43 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B 11.15 kV
Ia (rated) =10003×6.6=87.5A

Vt=66003=3810.6V

Operation at 0.8 lagging pf rated terminal voltage
Ef=Vt+jIaXs

=3810.6+j87.5(0.8j0.6)25

=5123+j1750=5413.718.86

|Ef|=5413.7V

Operation at 0.8 leading pf with excitation remaining unchanged

Also jIaXs=j87.5(j0.8+j0.6)×25

=2187.5126.87

=2187.553.13


From the phasor diagram:
5413.7sin53.13=2187.5sinδ

δ=18.8

Also, Vtsin108.1=2187.50.323

Vt=6437.3V (or) 11.15kV(line)