CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 200 bus power system has 160 PQ buses. To obtain the load flow solution by using Newton Raphson method in polar coordinates, the minimum number of simultaneous equations to be solved is _______.
  1. 359

Open in App
Solution

The correct option is A 359
Total buses = 200

PQ buses = 160

generator buses (PV) = 200 - 160 = 40 buses

among 40 PV buses one have to choose as slack bus.

The remaining generator buses = 39

Total no. of equations = 2PQ+PV = (160 × 2) + (39 × 1)

= 359

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Electrical Resistivity and Electrical Conductivity
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon