Question

A 25 MVA, 13.2 kV alternator with solidly grounded netural has a substransient reactance of 0.25 p.u. The negative and zero sequence reactance are 0.35 and 0.1 p.u. respectively. A single line to ground fault occurs at the terminals of an unloaded alternator, then the fault current is

A
3530 A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
5025 A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
4685 A
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
8025 A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 4685 A
For a line to ground fault,
Positive sequence current,

Ia1=EaZ1+Z2+Z0

Ia1=1j0.25+j0.35+j0.1=j1.428

Base current, Ib=25×1000×1033×13.2×103=1093.46A

Fault current, If=3Ia1×Ib

=3×1.428×1093.46

=4684.38A


flag