A 3 - phase, 3000 kVA, 0.95 lagging pf load is supplied by a Vee connection at 400V. The kVA output and operating power factor angle of both transformers respectively are

A
10009.1kVA and 1009.1kVA
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
10009.1kVA and 10009.1kVA
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
173248.19kVA and 173211.89kVA
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
173248.19kVA and 173211.8kVA
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 173248.19kVA and 173211.89kVA
kVA supplies by Vee connection transformer,

SVee=13×S3ϕ=30003=1732 kVA

p.f angle of transformer-1 =ϕ+30=cos1(0.95)+30=48.19

cos ϕ1=cos48.19=0.67 lagging

p.f. angle of transformer-2 =ϕ30=cos1(0.95)30=11.8

cos ϕ2=cos 11.8=0.98 leading

S1=173248.19 kVA

S2=173211.8kVA