wiz-icon
MyQuestionIcon
MyQuestionIcon
2
You visited us 2 times! Enjoying our articles? Unlock Full Access!
Question

A 3-phase balanced R-L load is connected to a 3-phase balanced symmetrical 400 V, 50 Hz, RYB sequence mains as shown in figure. The wattmeter W reads 1.732 kW. Then,

A
the active power in the load is 1.732 kW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
the reactive power of the load is 1.732 kVAr
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
the active power in the load is 3 kW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
the reactive power of the load is 3 kVAr
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B the reactive power of the load is 1.732 kVAr
Wattmeter reading,

B=|VPC||ICC|cos ϕ

Now,

VPC=VB=VYVB

ICC=IR


For phasor diagram,

ϕ=(90θ)

So,

Wattmeter reading,

W=|VYB||IR|cos ϕ

W=3 VI cos (90θ)

W=3 VI sin θ=Q

So, meter reads reactive power of the load.

flag
Suggest Corrections
thumbs-up
2
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Building the Supply Curve
ECONOMICS
Watch in App
Join BYJU'S Learning Program
CrossIcon