A 3-phase equilateral transmission line has a total corona loss of 53 kW at 106 kV and loss of 98 kW at 110.9 kV. The critical disruptive voltage between the lines is
A
66.8 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
22.2 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
32 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
53.4 kV
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution
The correct option is D 53.4 kV We know that, Power loss due to corona is P∝(Vph−Vc)2 ⇒P2P1=(Vph2−Vc)2(Vph1−Vc)2 ⇒9853=(110.9√3−Vc)2(106√3−Vc)2 ⇒Vc=53.4kV