A 3-phase, 5 kW induction motor has a p.f. of 0.75 lagging. A bank of capacitors is connected in delta across the supply terminals and p.f is raised to 0.9 lagging. The kVAR rating of capacitor connected in each phase is ____ kVAR.
0.66
Open in App
Solution
The correct option is A 0.66
Reactive power before compensation =5×103×tan(41.41∘)
=4.409kVAR
Reactive power after compensation =5×103×tan(25.84∘)
=2.421kVAR
∴ Reactive power supplied by capacitor bank,
=1.988kVAR
kVAR rating of capacitors connected in each phase =1.9883=0.662kVAR