A 3-pin mains plug is fitted to the cable for a 1 kW electric kettle to be used on a 250 V a.c. supply. Which of the following statement is not corrent ?
(a) The fuse should be fitted in the live wire
(b) A 13 A fuse is the most appropriate value to use
(c) The neutral wire is coloured black
(d) The green wire should be connected to the earth pin.
(b) is not correct.
The current passing through the electric kettle will be I = P/V
I = 1000/250 =4A
So 13A fuse is not the most appropiate value to use because it is too high for the passing current.