CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 4 pole turbo generator rated at 20 MVA, 13.2kV, 50 Hz has an inertia constant of H = 8.5 kW-s/kVA. It is supplying rated power at 0.8 pf. When a fault occurs that reduces the electical output to 40% of its initial value. Find the accelerating torque at the time when fault occurs?

A
61 kNm
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
75 kNm
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
122 kNm
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
100 kNm
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A 61 kNm
Output power before fault =20×0.8=16MW

Output power after fault =40100×16=6.4MW

Accelerating power, PAG=166.4

PAG=9.6MW

Accelerating torque, TA=PAGω=9.6×1062π×150060

=9.6×10650π

TA=61115.5Nm

=61 kNm

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Work Energy and Power
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon