wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 400 V, 50 Hz 3-ϕ balanced source supplies to a star connected load whose rating is S= (300 + j400) KVA. The rating of the delta connected capacitor bank necessary to bring the power factor to 0.9 lagging is _______ kVAR.
  1. 254.72

Open in App
Solution

The correct option is A 254.72
Load rating,

S = (300 + j400) KVA

Active power, P = 300 kW

Power factor=cos[tan1(400300)]=0.6 lagging

Required capacitor bank rating,

Qc=P1tanθ1P1tanθ2

=300 [tan53.13otan25.84o]

=254.72kVAR

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Capacitors in Circuits
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon