A 44 MVA, 10.5 kV, Y-connected three-phase salient pole synchronous generator has
Xd=1.83Ω and
Xq=1.21Ω. It delivers the rated load at 0.8 p.f. lagging. The armature resistance is negligible, the load angle of the given alternator is ______ degrees (upto two decimal places).
- 16.69