A 50 Hz, 3-phase, 33 kV synchronous generator is connected to a power system. The system inductance and capacitance per phase are 8 mH and 0.5 mF respectively. The value of restriking voltage at time t = 1.57 ms is
A
6.72 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
7.88 kV
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
26.94 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
20.66 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!