CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
2
You visited us 2 times! Enjoying our articles? Unlock Full Access!
Question

A 50 Hz, 3-phase, 33 kV synchronous generator is connected to a power system. The system inductance and capacitance per phase are 8 mH and 0.5 mF respectively. The value of restriking voltage at time t = 1.57 ms is

A
6.72 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
7.88 kV
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
26.94 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
20.66 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B 7.88 kV
VR=Vm(1cosωt)

ω=1LC

Vm= per phase peak voltage

ω=10.5×103×8×103=500rad/sec

Vm=(333)×2kV=26.94kV

at t=1.57 msec,
VR=26.94(1cos(500×1.57×103))

VR=7.88kV (Keep the calculator in radian mode)

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
PN Junction
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon