A 50 Hz, four pole turbo generator rated 100 MVA, 11 kV has an inertia constant of 8.0 MJ/MVA. Mechanical input is suddenly raised to 80 MW for an electrical load of 50 MW. If the acceleration is maintained for 10 cycles, the rotor speed at the end of this period is
M=GHπf=100×850×180=445MJs/elec.degree
Md2δdt2=(Pm−Ps)
d2δdt2=30×454
d2δdt2=337.5elecdeg/s2
dδdt=337.5t
dδdt=337.5×1050×60360×(24)=5.625rpm
ωm=ωm0+dδdt
Nm=120×504+5.625=1505.625rpm