wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 50 Hz generator is delivering 60% of power that it is capable of delivering through a transmission line to an infinite bus. A fault occurs that increases the reactance between the generator and the infinite bus to 400% of the value before the fault. When fault is isolated, the maximum power that can be delivered is 75% of the original maximum value. For this condition critical clearing angle (in degres) is

A
67.33o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
54.17o
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
36.86o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
51.32o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B 54.17o
Given, before fault,

0.6 Pm1=Pm1 sinδ0
δ0=36.86o (or)0.643 radian

During fault, Pm2=0.25 Pm1 as X2=4X2

After fault,

Pm3=0.75 Pm1 (given)

δmax=180sin1(0.6Pm10.75Pm1)

=126.86o (or) 2.214 radian

Since, cos δcr=Ps(δmaxδ0)+Pm3cosδmaxPm2cosδ0Pm3Pm2

cos δcr=0.6Pm1[2.2140.643]+0.75Pm1cos(126.86)0.25Pm1cos(36.86)0.75Pm10.25Pm1

=0.6(2.2140.643)+0.75cos(126.86)0.25cos(36.86)0.750.25


cos δcr=0.585
δcr=54.2o

flag
Suggest Corrections
thumbs-up
6
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Equal Area Criteria: Effect of Clearing Time On Stability
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon