A 50 kVA, 440 V, 3 - phase, 50 Hz induction motor is provided with a 3 - phase step - down auto - transformer starter which steps down the voltage to 50% of the input. The starting current of the motor on rated voltage is 6 time the rated full - load current. Estimate the current drawn by the auto - transformer from the mains at starting. What is the starting kVA drawn by the auto - transformer ?

A
170.455 A, 95.73 kVA
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
125.613 A, 107 kVA
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
140.401 A, 129.903 kVA
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
98415 A, 75 kVA
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 98415 A, 75 kVA

Given x=50%=0.5;

IfL=50×1033×440=65.61 A

Given Ist(m)=6Ifl=6×65.61

=393.65 A

Ist(AT)=x2Ist(m)=(0.5)2×393.65=98.412A

(kVA)st=3Ist(AT)×440

=3×98.412×440=7500 VA

=75 kVA