CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 50 MVA, 10 kV, 50 Hz, star-connected, unloaded three-phase alternator has a synchronous reactance of 1 p.u. and sub-transient reactance of 0.2 p.u. If a 3-phase short circuit occurs close to the generator terminals, the ratio of initial and final values of the sinusoidal component of the short circuit current is
  1. 5

Open in App
Solution

The correct option is A 5
I′′=EgX′′d;I=EgX

Fault current is inversely proportional to the reactance during the fault.

I′′I=XX′′d=1.00.2=5.0p.u.

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Three-Phase Short Circuit (Symmetrical Fault) On Synchronous Machines - Unloaded & Loaded
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon