The most economic division of load is
0.10PG1+20=0.12PG2+15
0.10PG1−0.12PG2=−5
PG1+PG2=300
PG1=140.9MW
PG2=159.1MW
Equal load sharing PG1=PG2=150MW
Increase in cost for unit-1;
=150∫140.9(0.1PG1+20)dPG1
=0.1(PG1)22∣∣
∣∣150140.9+20(PG1)|150140.9=314.36Rs/hr
Increase in cost for unit-2
150∫159.1(0.12PG2+15)dPG2=−305.27Rs/hr
Net saving = (314.36−305.27)×24
=Rs218.16/day