A generating station having n-section busbars each rated at 8 kVA with x% reactance is connected on the tie-bars system through busbar reactance of b%. If n is very large and a three phase fault takes place on one section then the short circuit kVA is

A
8x
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
8b
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
8x+b
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
8(1x+1b)
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 8(1x+1b)

Equivalent impedance Zeq between the zero potential bus and the fault point is

(b+xn1+b)x=(bn+xn1)x

1Zeq=1x+n1bn+x

SCKVA=8Zeq×100

=8[1x+n1bn+x]×100

If n is very large,

Short circuit KVA =8[1x+1b]