wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A generator is connected through a 20 MVA, 13.8/138 kV step down transformer, to a transmission line. At the receiving end of the line a load is supplied through a step down transformer of 10 MVA. 138/69 kV rating. A 0.72 p.u. load, evaluated on load side transformer ratings as base values, is supplied from the above system. For system base values of 10 MVA and 69 kV in load circuit, the value of the load (in per unit) in generator circuit will be.

A
36
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
1.44
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.72
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
0.18
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A 36
Base values on load circuit,

(MVA)B=10MVA and

(kV)B=69kV

Base impedance=69210=476.1

Values of load in ohm=ZL

= Value of load in p.u.× Base impedance

ZL=0.72×476.1=342.8Ω

Base values in generator circuit,

(MVA)B=20MVA

(kV)B=13.8kV

Base impedance

=ZB=(kV)2B(MVA)B=13.8220

ZB=9.522Ω

ZLZB=324.89.522=36p.u.

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
PU Equivalent Circuits of 1-Phase Transformer & 3-Phase Balanced Transformer
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon