A generator of negligible resistance having 1 p.u. voltage behind transient reactance is subjected to different types of faults when its neutral is solidly grounded
Type of fault Resulting fault current in p.u.
L - L 2 p.u
L - G 3 p.u
Then the value of zero sequence reactance (in p.u.)is________
- 0.134