CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A lossless transmission line having operating voltage VS=VR=400kV has surge impedance of 400 Ω. It is connected with a 25% of shunt capacitance compensation at the load end. If the generator is delivering a power of 200 MW through these lines, then the load angle δ of the generator in degree is

A
24.76o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
28.72o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
26.56o
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
23.42o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 26.56o
SIL=400×400Zsc

Zsc=Zs1+Kcsh=4001+0.25=357.77Ω

SIL=400×400357.77×106=447.21MW

P=Pmaxsinδ

or 200=447.21sinδ

or δ=sin1(200447.21)=26.56o

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Phasors and Phasor Diagrams
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon