Question

A lossless transmission line with 0.3 pu reactance per phase uniformly distributed along the length of line, connecting a generator bus to a load bus, is protected upto 85% of its length by a distance relay placed at the generator bus. The generator terminal voltage is 1 pu. If no generator is at the load bus, the threshold pu current for operation of distance relay for a solid three phase to ground fault on the transmission line will be________ (upto 2 decimal places)
  1. 3.92

Open in App
Solution

The correct option is A 3.92

Per unit fault current, If=1Zth=10.3=103

for 100% of transmission line =103pu

Relay is operated for 85% length of transmission line,

Zf=0.85Zl=0.85×0.3=0.255 pu

For 85/ of transmission line,

If=10.255=3.92 pu