Question

A refrigerator operates between 120 kPa and 800 kPa in an ideal vapor compression cycle with R134a as the refrigerant. The refrigerant enters the compressor as saturated vapor and leaves the condenser as saturated liquid. The mass flow rate of the refrigerant is 0.2kg/s. Properties for R134a are as follows:

Saturated R- 134aP(kPa)T(C)hf(kJ/kg)hs(kJ/kg)sf(kJ/kgK)sg(kJ/kgK)12022.3222.52370.0930.9580031.3195.5267.30.3540.918Superheated R- 134aP(kPa)T(C)h(kJ/kg)s(kJ/kgK)80040276.450.95

The power required for compressor in kW is

A
5.94
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
1.83
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
7.9
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
39.5
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 7.9
Power required for the compressor,

P=m(h2h1)=0.2(276.45237)

=7.89 kW=7.9 kW