A single-phase, 50 kVA, 2200 V/400 V, 50 Hz transformer is tested for open and short-circuit test with below shown inferences:
Open circuit test : hv open circuited
V = 400 V, I = 1.2 A, W = 240 W
Short circuit test : Iv side short circuited
V= 100 V, I = rated current, W = 280 W
The value of half full load efficiency of transformer operating at unity power factor will be ____%
(upto 2 decimal place).
- 98.78