Question

A square steel slab of area 1 m2 is provided for a column made of two rolled channel sections. The 300 mm x 300 mm column carries an axial compressive load of 2000 kN. The line of action of the load passes through the centroid of the column section as well as of the slab base. For plate take
Fy=250 N/mm2.
The required minimum thickness of the slab base is :

Open in App
Solution

300 mm x 300 mm column leaves projection as



a=b=10003002=350 mm

w=PuA=1.5×20001×1=3000 kN/m2=3 N/mm2

ts=[2.5w(a20.3b2)γm0Fy]1/2>tf

ts=[2.5×3×(35020.3×3502)×1.1250]1/2

ts=53 mm

t55 mm