Question

A steel column is to support a factored load of 1200kN. The column ends are flushed for complete bearing at a section where it is to be spliced as shown in figure. The allowable stress in the splice plate is 240MPa. The thickness (in mm, rounded off to the multiple of 2) of the splice is: (Take the width of splice plate is 250mm)

A
4mm
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
6mm
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
8mm
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
10mm
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B 6mm
Since column ends are flushed, hence 50 % of load is transfered through the splice and fastenings.

The load on each splice plate =1200×1034=300×103N

Sectional area of splice plate =300×103240N/mm2

=1250mm2.

Thickness of splice plate =1250250=56mm