A sustained 3−ϕ fault occurs in the power system as shown below and corresponding current and voltage phasors during the fault ( on a common reference) are also shown after natural transients. The location of fault in the system is at location
A
A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
C
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
D
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
B
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution
The correct option is D B During fault, the current value increases, the voltage drop and power factor decreases, reactive power drawn increases generally due to reactance of line. ∴ Fault current is high having 90° lagging nature in a transmission line for phasor diagram.
The phasor of →I2 is having largest magnitude and lags voltage →V1 by almost 90°.
So quantities →V1 and →I2 resembles faulty condition. ∴ location B is most feasible fault position according to phasor diagram.