wiz-icon
MyQuestionIcon
MyQuestionIcon
7
You visited us 7 times! Enjoying our articles? Unlock Full Access!
Question

A sustained 3ϕ fault occurs in the power system as shown below and corresponding current and voltage phasors during the fault ( on a common reference) are also shown after natural transients. The location of fault in the system is at location




A
A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
C
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
D
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
B
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D B
During fault, the current value increases, the voltage drop and power factor decreases, reactive power drawn increases generally due to reactance of line.
Fault current is high having 90° lagging nature in a transmission line for phasor diagram.
The phasor of I2 is having largest magnitude and lags voltage V1 by almost 90°.
So quantities V1 and I2 resembles faulty condition.
location B is most feasible fault position according to phasor diagram.

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Electric Power
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon