wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A three phase, 200 MVA, 11 kV generator has the following p.u. constants. The generator neutral is solidly grounded X1=X2=3X0=0.30 Ω. The ratio of the fault current due to three phase dead short circuit to that of L-G fault would be _____.
  1. 0.78

Open in App
Solution

The correct option is A 0.78
If 3ϕ=EfX1

If LG=3EfX1+X2+X0

If 3ϕIf LG=X1+X2+X03X1

=0.30+0.30+0.103×0.30=0.7780.78

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Single Line to Ground (L-G) Fault - Unloaded & Loaded
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon