Question

A three phase 300 kVA, 30 kV/1 kV (Δ/Y) 50 Hz transformer has primary (hv side) resistance per phase of 0.4 Ω and secondary (Iv side) resistance per phase of 0.1 Ω. Iron loss of the transformer is 5000 W. The full load percentage efficiency of the transformer operated at unity power factor will be _____.
  1. 95.14

Open in App
Solution

The correct option is A 95.14
For given 3ϕ transformer



Given, R1=0.4 Ω/phase

R2=0.1 Ω/phase

Iron loss = 5000 W

Primary line current, IL1=300×10003×3000=1003A

Primary phase current, Iph,1=IL13=1003A

Secondary line current, IL2=300×10003×1000=3003A

Secondary phase current =3003A (Star connection)

Copper loss on hv side =3I21R1 =3(1003)2×(0.4) =3×100×1009×0.4=13333.33 W

Copper loss on lv side =3I22R2=3(3003)2×(0.1)=9000 W

At unity power factor,

Efficiency, η=(300×1000×1)(300×1000×1)+5000+1333.33+9000

η=0.951374

%η=95.14%