wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A three-phase star connected synchronous generator is rated at 1.5 MVA and 11kV. The armature effective resistance and synchronous reactance are 1.2 Ω and 25 Ω respectively (per phase). The percentage voltage regulation for a load of 1.4375 MVA at 0.8 power factor lagging is _______.
  1. 21.14

Open in App
Solution

The correct option is A 21.14

Given, V=11×1033=6350.853 V
R=1.2 Ω,

jX=j25 Ω

|I|=1.4375×1063×6350.853=75.45 A

I=75.4536.87

E=6350.853+(1.2+j25)(75.4536.87)

=7693.80710.898 V

Voltage regulation =|E||V||V|=×100

=7693.8076350.8536350.853×100=21.14 %


flag
Suggest Corrections
thumbs-up
8
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Transformer
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon