An 11 kV, 100 MVA generator is provided with differential scheme of protection. The percentage of generator winding to be protected against phase to ground fault is 80%. The relay is set to operate when there is 15% out of balance current. The value of the resistance to be placed in the neutral to ground connection is ______ohms.