CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

An 11 kV, 100 MVA generator is provided with differential scheme of protection. The percentage of generator winding to be protected against phase to ground fault is 80%. The relay is set to operate when there is 15% out of balance current. The value of the resistance to be placed in the neutral to ground connection is ______ohms.

A
6.44
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
2.788
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.4025
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
1.61
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 1.61
Primary earth-fault current at which the relay operates,

=100×1063×11×103×15100=787.29 A

The percentage of winding which remains unprotected is

P = 100 - 80 = 20%


The fault current =20100×11×1033Rn

Where Rn is the resistance in the neutral to ground connection

20100×11×1033Rn=787.29

Rn=20×11×103100×3×787.29=1.61 ohms

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Conductivity and Resistivity
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon