Question

An 11 kV, 100 MVA generator is provided with differential scheme of protection. The percentage of generator winding to be protected against phase to ground fault is 80%. The relay is set to operate when there is 15% out of balance current. The value of the resistance to be placed in the neutral to ground connection is ______ohms.

A
6.44
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
2.788
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.4025
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
1.61
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 1.61
Primary earth-fault current at which the relay operates,

=100×1063×11×103×15100=787.29 A

The percentage of winding which remains unprotected is

P = 100 - 80 = 20%


The fault current =20100×11×1033Rn

Where Rn is the resistance in the neutral to ground connection

20100×11×1033Rn=787.29

Rn=20×11×103100×3×787.29=1.61 ohms