wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

An absorption refrigeration system having evaporator temperature of -5°C and ambient temperature of 25°C. The heat is supplied to generator from steam at 0.1 MPa, 0.95 quality. The saturated temperature of steam at 0.1 MPa is 100°C and hfg=2000 kJ/kg. What is the steam flow rate required if the actual COP is 80% of maximum COP and the refrigerator effect is 60 kW?

A
0.041 kg/s
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
0.01 kg/s
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.022 kg/s
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
0.06 kg/s
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 0.022 kg/s
TE=268 K

Ta=273+25=298 K

TC=373 K

(COP)max=(TETdTE)×(TGTdTG)=(268298268)×(373298373)=1.796

(COP)a= Actual COP = 0.8 (COP) max
= 1.437

1.437=REWin=60QG

QG=41.75 kW

ms×0.95×hfg=QG=41.75

ms=0.022 kg/s