An alternator has a synchronous reactance of 20% and negligible resistance. Its voltage regulation when working on full load at 0.8 pf lag will be _________%
  1. 13

Open in App
Solution

The correct option is A 13
E2f=(Vt cos ϕ)2+(Vt sin ϕ+IaXs)2

E2f=V2t[0.82+(0.6+IaXsVt)2]

E2f=V2t[0.82+(0.6+0.2)2]

Ef=1.13 Vt

Voltage regulation =EfVtVt×100%

=1.13VtVtVt×100%=13%