CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
3
You visited us 3 times! Enjoying our articles? Unlock Full Access!
Question

An IDMT relay is used to protect feeder through 500/1 CT. The relay has a PSM 100% and TMS = 0.4, relay characteristics are given for TMS = 1.

PSM23581012Time (sec)1064.53.232.5

If the fault current is 5000 A, then time of operation of relay will be_______sec.
  1. 1.2

Open in App
Solution

The correct option is A 1.2
Given, IF=5000A

CT = 500/1

% relay setting = 100

Isec(CT)=IF×I2I1=5000×1500=10A

PSM=Isec(CT)Ipickup

=10relay setting×Irated(relay)

=101×1=10

Time of operation of relay, corresponds to PSM = 10 is 3 seconds (from characteristics table)

Time of operation of relay for TMS = 1 is 3 sec

Then time of operation of relay (for TMS = 0.4) is = Top

Top=3×TMS

Top=3×0.4=1.2sec

flag
Suggest Corrections
thumbs-up
5
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
The Direction of Induced Current
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon