CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

A 11 kV, 100 MVA alternator is provided with differential protection. The percentage of winding to be protected against phase to ground fault is 85%. The relay is set to operate when there is 20% out of balance current. The value of resistance to be placed in the neutral to ground connection is ______ Ω.
  1. 0.91

Open in App
Solution

The correct option is A 0.91
Primary earth fault current at which relay operates

=100×1033×11×20100=1049.73A
Percentage of winding which remains unprotected is

ϕ=10085=15

The fault current =ϕ100×11×1033Rn

15100×11×1033Rn=1049.73

Rn=0.91Ω


flag
Suggest Corrections
thumbs-up
9
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Electrical Instruments
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon