A 11 kV, 100 MVA alternator is provided with differential protection. The percentage of winding to be protected against phase to ground fault is 85%. The relay is set to operate when there is 20% out of balance current. The value of resistance to be placed in the neutral to ground connection is ______ Ω.
0.91
Open in App
Solution
The correct option is A 0.91 Primary earth fault current at which relay operates
=100×103√3×11×20100=1049.73A
Percentage of winding which remains unprotected is