At 50 Hz operation, a single phase transformer has hysteresis loss of 200 W and eddy current loss of 100 W. Its core loss at 60 Hz operation at constant flux density will be_______W.
384
Open in App
Solution
The correct option is A 384 Hysteresis loss is proportional to frequency and eddy current loss is proportional to the square of the frequency. ∴ The core loss at 60 Hz Pcore=khf+kef2 (kh = hysteresis loss constant, ke = eddy current loss constant)