Five synchronous generators are connected in parallel as shown in below figure. The rating of each generator is 22 kV, 20 MVA, 0.5 pu reactance. If fault occurs at location 'P', then current carried by shown circuit breaker CB when fault occurs at point 'P' will be______ pu.



A
-j12 pu
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
-j10 pu
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
-j8 pu
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
-j2 pu
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C -j8 pu
For the given system when fault occurs at point P, fault current
If=1/Zth


Per unit Thevenin impedance,
Zth=j0.55=j0.1
Fault current, If=1j0.1=j10 pu

Drawing impedance diagram



By current division rule

Fault current, If=j10×j0.5j0.5+j0.54

=j10×0.5jj0.625=j8 pu