Question

For a power system:

Line to line fault current=j2.5 p.u.
3ϕ fault current =j5 p.u.
The positive and negative sequence reactances are

A
X1=0.3 p.u., X2=0.1 p.u.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
X1=0.2 p.u., X2=0.49 p.u.
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
X1=0.1.p.u.,X2=0.3 p.u.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
X1=0.25 p.u.,X2=0.15 p.u.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B X1=0.2 p.u., X2=0.49 p.u.
3ϕ fault current:

Let system is under no load condition before fault,

E=10p.u.

3ϕ fault current,If=EX1

X1=1j5=j0.2 p.u.

Lineline fault current:If=3EX1+X2

X1+X2=3j2.5

j0.2+X2=j0.69 p.u

X2=j0.49 p.u