In a 100 bus power system, there are 10 generators. In a particular iteration of Newton Raphson load flow technique (in polar coordinates), two of the PV buses are converted to PQ type. In this iteration,
A
the number of unknown voltage angles increases by two and the number of unknown voltage magnitudes increases by two.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes increases by two
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
the number of unknown voltage angles increases by two and the number of unknown voltage magnitudes decreases by two
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes decreases by two
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution
The correct option is B the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes increases by two The voltage angles are the common variable for both PV and PQ buses, so it remains unchanged. Where as voltage magnitude is specified in PV bus and not specified in PQ bus, so it increases by two.