In a double pipe counter flow heat exchanger oil of heat capacity rate 2.1 kJ/sK is cooled from 120C to 60C with help of cooling water 4.2 J/kgK which is flowing at a rate of 1.5 kg/s. The heat transfer surface area is 22 m2 and cooling water enters at 40C. What is the value of appropriate overll heat transfer coefficient?

A
123.3 W/m2K
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
167.3 W/m2K
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
157.3 W/m2K
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
181.3 W/m2K
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 157.3 W/m2K


Cph=2.1 kJ/K

Thi=120C Tho=60C

Tci=40C

mc=1.5 kJ/s, Cpc=4.2 kJ/kgK

From energy balance,

Q1=Cpj(ThiThv)=mc.cpc(TcoTci)

2.1×(12060)=1.5×4.2×(T40)

T=60C

θ1=60 θ0=20

LMTD=θ1θ0ln(θ1θ0)=6020ln(6020)=36.41C

Q=UA LMTD

Cph(ThiT)=U×22×36.41

2.1×(12060)=U×22×36.41×103

U=157.3 W/m2K