In a system, there are two generators operating in parallel. One generator, of rating 250 MVA, has an inertia constant of 6 MJ/MVA while the other generator of 150 MVA has an inertia constant of 4 MJ/MVA. The inertia constant for the combined system on 100 MVA common base is MJ/MVA.
- 21