Question

In the figure shown below,



If both the relays R1 and R2 are set for 100% plug setting, the actual operating time of R1 and TMS for R2 respectively are:
(Assume time grading margin of 0.6s and TMS for relay 1 is 0.15)

PSM3.66.7513.5Time in sec forTime Multiplier63.62.6

A
0.39 sec,TMSR2=0.275
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
0.41 sec,TMSR2=0.142
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.32 sec,TMSR2=0.123
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
0.54 sec,TMSR2=0.112
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A 0.39 sec,TMSR2=0.275
Plug setting multiplier of relay 1
=27001×1×2001=13.5

Operating time corresponding to 13.5 PSM is 2.6

Actual operating time of relay 1
=2.6×TMS=2.6×0.15=0.39sec

V2V1=I1I2

33132=I12700

I1=675A

PSM of relay 2=6751×1×1001=6.75

Operating time corresponding to PSM 6.75 is 3.6 s.

TMS for relay 2=0.39+0.63.6=0.275