wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

In the system shown, the generator is delivering 1 p.u. power. The voltage behind transient reactance is 1.05 p.u. and infinite bus voltage is 1 p.u. If the system is subjected to a 3ϕ fault on point P, the critical clearing angle is______electrical degrees.[H=5 MJ/MVA.f = 50 Hz]


A
60.24
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
45.40
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
81.72
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
75.80
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 81.72
System reactance. X = j(0.2+0.1+0.42)=j0.5 p.u.

Ps=VsVRXsinδ=1.05×1.00.5sinδ=2.1 sinδ

Ps=1 p.u
δ=sin1(12.1)=28.44=0.496 radian (elec)

δc=cos1[(π2δ0)sinδ0cosδ0]
=cos1[(π2×0.496)sin28.44cos28.44]
=81.72 (electrical)

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Equal Area Criteria: Effect of Clearing Time On Stability
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon