CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
254
You visited us 254 times! Enjoying our articles? Unlock Full Access!
Question

Incremental fuel costs (in some appropriate unit) for a power plant consisting of three generating units are

IC1=20+0.3P1,
IC2=30+0.4P2,
IC3=30

where Pi is the power in MW generated by units for i = 1, 2 and 3.

Assume that all the three units are operating all the time. Minimum and maximum loads on each units are 50 MW and 300 MW respecitvely. If the plant is operating on economic load dispatch to supply the total power demand of 700 MW, the power generated by each unit is

A
P1 = 242.86 MW; P2 = 157.14 MW; and P3 = 300 MW
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
P1 = 157.14 MW; P2 = 242.86 MW; and P3 = 300 MW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
P1 = 300.0 MW; P2 = 300.0 MW; and P3 = 100 MW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
P1 = 233.3 MW; P2 = 233.3 MW; and P3 = 233.4 MW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A P1 = 242.86 MW; P2 = 157.14 MW; and P3 = 300 MW
When P1 is minimum i.e. P1 = 50 MW

IC1=20+0.3×50=35

When P2 is minimum i.e. P2 = 50 MW

IC2=30+0.4×50=50

For minimum value of P1andP2

IC1 and IC2>IC3

Therefore,

P3 = 300 MW

[maximum load is assigned to unit 3]

Remaining power is to shared by unit 1 and 2.

So,P1+P2=700300=400MW.....(i)

For optimal operation,

IC1=IC2

20+0.3P1=30+0.4P2

0.3P10.4P2=10

Solving equation (i) and (ii), we get

P1 = 242.86 MW

and P2 = 157.14 MW

flag
Suggest Corrections
thumbs-up
7
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
ELD Within the Plant Without Transmission Losses
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon